Products Description
There are many types of cables, and the website cannot display all of them. We have most cables in stock, and special cables can be customized. If you have any cable needs, please contact us.
1 Product Standard
This product is manufactured according to GB/T12706.2, equivalent to IEC60502.2. Or BS, DIN, ICEA standard as customer request.
2 Application
The product is suitable for use in power transmission and distribution lines with rated power frequency voltage 3.6/6kv~26/35kv.
3 Operating characteristics
- Rated power-frepuency voltage U0/U: 3.6/6kv~26/35kv.
- Max.admissible operating temperature of the conductor:90ºC.
- Max. short-circurt temperature of conductor shall not exceed 2500C. (5s maximum duration)
- The ambient temperature under installation should not below 00C.
- The bending radius of a single-core cable should not less than 20 times of the cable diameter.
The bending radius of a multi-core cable should not less than 15 times of the cable diameter.